|
J.R.E. Corbett3, L.A. Slezak1, M.K. Fries2, L.R.
Pickard3, L. Mah3, and R.A. Palsenbarg4
Contact: corbettr@ae.ca
1Brown and Caldwell Consultants Canada Ltd.
2 Reid Crowther Partners Ltd.
3Associated Engineering, Burnaby, B.C.
4 Greater Vancouver Regional District
ABSTRACT
The Greater Vancouver Sewerage & Drainage District (GVS&DD) is
a major regional wastewater agency serving Vancouver, British Columbia
and surrounding municipalities. In the late 1980s it was mandated
to upgrade its largest treatment plant from primary treatment to secondary
treatment. From 1990 until the present the GVS&DD has engaged in Predesign,
Design, Construction and Commissioning of the Annacis Island WWTP Secondary
Upgrade. The size of the facility and the fact that no secondary treatment
components were previously in place combined to make the upgrade a very
large project valued at nearly $470 million CDN. This paper describes
the major project components of the liquid stream process improvements.
In addition to the major biological treatment components, other aspects
of the project are described including, odour management, influent pumping,
and primary treatment upgrades.
KEYWORDS
Wastewater treatment; design; secondary treatment; trickling filter/solids
contact process; odour control; biofilter
INTRODUCTION
The major portion of the secondary treatment upgrade involved adding
facilities to accomplish biological secondary treatment for flow exiting
the existing preaeration and primary sedimentation processes. Originally,
the project was conceived as a single step addition of an entire secondary
treatment process train. Funding constraints required that an alternative
implementation strategy be adopted - a portion of the facilities was to
be commissioned at an earlier date to provide secondary treatment for
a portion of the primary effluent flows. This change in approach led to
the Phase I Secondary Treatment upgrade, which is discussed later in this
paper and which is planned to operate for a little more than one year
before the full secondary treatment process is commissioned.
TRICKLING
FILTER/SOLIDS CONTACT (TF/SC) PROCESS SELECTION
A principal activity of the predesign effort was to select the
biological treatment process (Parker et.al., 1993). There were few constraints
imposed on the selection process since no form of secondary treatment
was already in place.
The major design requirements for the process were the quality of effluent
and the range of flows to be treated. Within Canada, effluent criteria
are set by the provinces rather than the federal government. The British
Columbia Ministry of Environment, Lands and Parks set fairly stringent
criteria for the Annacis Island plant. Composites for any single day cannot
exceed BOD5 values of 30 mg/L and TSS values of 40 mg/L. These daily criteria
are considerably more stringent than requirements for secondary treatment
in the US, where the USEPA criteria require BOD5 and TSS values of less
than 30 mg/L for monthly averages rather than for daily values.
The requirement to meet effluent criteria on a daily basis created the
need for the treatment process to perform optimally at rated peak wet
weather flows (PWWF) which are two times the rated average dry weather
flows (ADWF) of 5.6 m3/s. PWWF can be maintained for intervals of 12 hours
or more. Above the rated PWWF, the criteria allow for blending of primary
effluent flows that are greater than the PWWF receiving complete secondary
treatment.
A total of 17 secondary treatment processes were screened for consideration.
Initial screening was done on the basis of noneconomic criteria. Preestablished
screening criteria included process characteristics, operation/maintenance
considerations, planning criteria, and environmental factors. The screening
criteria were weighted using nominal group technique involving participation
of GVS&DD stakeholders. After screening, three processes remained;
the air activated sludge process (AAS), the oxygen activated sludge process
(OAS), and the trickling filter / solids contact process (TF/SC).
Present value cost analysis yielded the cost comparison
summary shown in Figure 1. While OAS was a slightly lower
cost process to build, TF/SC showed operation and maintenance
savings that resulted in an estimate of an overall lower
total present value cost for TF/SC.
In
addition to the economic analysis, the three process alternatives were
subjected to a technical evaluation using non-economic factors developed
in the screening evaluation. A consensus procedure was used by GVS&DD
staff and consultants in two workshops to establish numerical scores for
each factor. In the first workshop, issues, concerns, or unknowns about
each process were listed. Information on each identified technical concern
was then gathered. The evaluation group visited four OAS plants, two AAS
plants, and two TF/SC plants. The final workshop resulted in establishment
of ratings for the various categories of concern. Each process ranked
higher in some categories and lower in others than the other two alternatives.
Overall, however, the OAS and TF/SC processes were found to have essentially
equal ratings. The AAS process was found to be 15 percent lower in its
non-economic score than the other two processes.
The TF/SC process was ultimately selected as the biological secondary
treatment process. It was competitive with the next best alternative (OAS)
in terms of capital costs, and had significantly lower O&M costs because
of lower labour and energy requirements. Three key non-economic characteristics
favoured the TF/SC process: robustness or the ability of a process to
maintain high effluent quality under stressed conditions, ease of operation,
and ease of maintenance.
TF/SC PROCESS DESIGN
Figure 2 illustrates the TF/SC process. The TF/SC process consists of
high rate attached growth reactor (trickling filter) followed by a short
solids residence time (SRT) aerobic suspended growth reactor (solids contact
tank) which improves the settling characteristics of biomass wasted from
trickling filters as well as provide additional oxidation of carbonaceous
organic materials. The solids contact tanks are coupled with secondary
clarifiers which return biological solids to the front end of the solids
contact tanks. Low SRTs are maintained in the solids contact portion to
prevent nitrification thereby limiting aeration capacity requirements.
Trickling
Filters Design Features. Table 1 describes the basic
design data for the trickling filters. The trickling filters
remove soluble carbonaceous BOD by means of biofilm attached
to the media. Each of the trickling filters is covered for
odour control. Covering of the filters necessitated forced
air ventilation of the filters to assure supply of oxygen
for treatment and for conveyance of foul air to odour treatment.
Table 1 Trickling Filters
Design Data
| Number of Units |
4
|
| Media Type |
Plastic Crossflow
|
| Diameter, m |
52
|
| Media Depth, m |
6
|
| Total Media Volume,
m3 |
52,000
|
| Total Organic Loading,
kg BOD5/m3 - day |
|
|
at ADWF |
1.40
|
| at Maximum Month Flow |
1.63
|
| Ventilation Rate, m3/min,
each |
|
|
Supply |
255
|
| Recycle |
2,600
|
| Exhaust |
338
|
| Hydraulic Application
Rate, m3/m2 - day |
|
|
at Minimum Diurnal Flow |
18
|
| at ADWF |
57
|
| at PWWF (4 filters) |
118
|
| at PWWF (3 filters) |
158
|
|
After
pumping, wastewater is applied to the top of the plastic media
by means of six arm, mast type rotary distributors. The distributor
arms rotate by reactionary force of the discharging primary
effluent. Accommodations have been made for reversing discharge
nozzles as a means of controlling arm rotation rate in order
to assure adequate washing of the media. The magnitude and
low frequency of occurrence of minimum diurnal flows allowed
the trickling filters to be designed without a recirculation
system.\
An expanded section of the trickling filter effluent channel was designed
for the purpose of removing many of the snails which discharge from the
trickling filters. The expanded section is aerated much like a grit removal
tank and a submersible solids handling pump is located to remove the snails
to be disposed with primary grit.
Solids Contact Tank Design Features. Table 2 describes the basic
design criteria for the four solids contact tanks. These tanks were configured
to operate in reaeration mode. Return secondary sludge will be returned
to one or two of the tanks where it will be aerated prior to blending
with the trickling filter effluent. This configuration allows some of
the tankage to be maintained at higher MLSS levels, while allowing the
design SRT to be maintained and lowering the solids load to the secondary
clarifiers. The major control parameter will be the solids contact tank
MLSS rather than the SRT. Clarifier design was based on an MLSS concentration
of 2000 mg/L. Wasting rates and return rates will be manipulated to ensure
that this basic parameter is satisfied.
Table 2 Solids Contact
Design Data
| Number of Units |
4
|
| Dimensions |
|
|
Length, m |
73.0
|
|
Width, m |
14.5
|
|
SWD, m |
6.0
|
| Hydraulic retention
time (at ADWF), h |
1.25
|
| Solids retention time
(at ADWF), d |
1.05
|
| Reaeration Tank Design
Oxygen Supply |
|
|
Average, kg/d |
7,060
|
|
Peak, kg/d
|
11,326
|
| Contact Tank Design
Oxygen Supply |
|
|
Average, kg/d |
5,140
|
|
Peak, kg/d |
5,810
|
| Air Requirements |
|
|
Average, m3/min
|
392
|
|
Peak, m3/min |
500
|
|
Tank geometry was finalized after considering the space and geotechnical
constraints of the site and optimal depth to achieve low energy aeration.
The selected six metre depth provided the lowest overall cost and minimized
the space required for the tankage.
Special features were included in the tankage specifically due to the
nature of the trickling filter effluent entering the tanks. Snails can
grow in trickling filters and eventually are flushed into the trickling
filter effluent. Other TF/SC plants have experienced maintenance difficulties
due to substantial accumulations of snail shells in the contact tanks.
To preclude this problem at the Annacis Island plant, the floors were
sloped at three percent to a drainage trench along one wall. In turn,
this trench slopes to a central large drain. This configuration is intended
to minimize the problems associated with cleaning the snails from the
tank floor when access for maintenance is required.
The solids contact tank aeration system was designed to meet the oxygen
demands through a wide range of conceivable operating scenarios. Extensive
modeling was conducted to estimate the oxygen demand during average, peak
and minimum load conditions, in different process configurations (different
combinations of reaeration and contact) and through the various seasons
of the year.
Fine bubble aeration was chosen for the solids contact tanks. The contract
documents were prepared allowing for the tender of flexible membrane or
ceramic diffusers, both meeting basic performance and design criteria.
Flexible membrane systems with 225 mm diffusers proved the most cost effective
and were incorporated in the work. The standard oxygen transfer efficiency
(SOTE) limit specified for the reaeration tanks was 33 percent and for
the contact tanks, 35 percent. Clean water performance testing conducted
after installation proved that the system exceeded these stipulations.
An analysis of the air supply options led to the selection of single
stage blowers for the Annacis Island plant. The blowers were designed
to provide the necessary aeration air supply plus that required for agitating
deep, mixed liquor channels. Three 800 hp blowers, each capable of 6.5
m3/s, were provided. Separate, smaller multi-stage blowers also have been
incorporated to provide shallow channel agitation air.
Table 3Secondary Clarifiers
Design Data
| Number of Units |
12 |
| Diameter, m |
40 |
| Sidewater Depth, m |
5.7 |
| Surface Overflow Rate
m3/m2 - day |
|
|
ADWF |
32 |
|
Max Month Flow |
51 |
|
PWWF |
64.1 |
| Solids Loading Rate
kg/m2 - day |
|
|
ADWF |
80 |
|
Max Month Flow |
121 |
|
PWWF |
192 |
| Design Settled Volume
Index, ml/g |
135 |
|
Secondary
Clarifiers Design Features. Table 3 describes the basic
design criteria for the secondary clarifiers. The clarifiers
are circular flocculating well type with inboard launders.
Performance data at high loading rates were reviewed from
other treatment plants having similar clarifier designs in
order to build confidence that stringent effluent criteria
would be reliably achieved at the high loading rates experienced
with Number of Units PWWF. Solids loading rates are sustainable
so long as Settled Volume Index (SVI) remains below the design
value. Typically, TF/SC plants produce biological solids with
SVIs significantly lower than traditional suspended growth
processes.
Settled solids are removed from the clarifier floor
where they fall by means of two arm rotating suction headers directly
connected to return secondary sludge pumps. Scum removal is achieved with
a novel traveling beach and trough mechanism that removes scum from the
surface where it appears rather than pushing the scum to the perimeter
of the launders. With this system, most scum removal takes place within
the area contained by the flocculating well. A vertical line shaft non-clog
centrifugal pump is located at the center area of the clarifiers to pump
secondary scum off to the plant headworks.
PHASE I SECONDARY TREATMENT
Project funding mandated the phased implementation of the Annacis Island
Secondary Treatment Upgrade. To achieve the earliest possible improvement
in plant effluent quality, the components of the plant constructed under
this strategy included the solids contact tanks, the secondary clarifiers,
DAF thickening, and the digesters. This strategy allowed a portion of
the plant flow to receive secondary treatment as soon as possible, thereby
reducing the loads discharged to the Fraser River at the earliest possible
date.
Concept. The intent of Phase 1 was to operate the secondary components
of the plant as an activated sludge facility, without the trickling filters.
However, the aeration system is limited in the amount of oxygen it can
supply and would not be able to satisfy the requirements when the activated
sludge configuration was used to treat the entire primary effluent flow.
Accordingly, a relatively constant primary effluent flow has been diverted
to the secondary treatment area of the plant while the remainder is directed
to the plant effluent.
The activated sludge process design envisioned operation in a relatively
high rate mode, with SRTs between 2 and 2.5 days. At this SRT, oxygen
demands are low, as the potential for nitrification is limited; although
higher residual dissolved oxygen concentrations are needed to inhibit
bulking. Seasonal analyses were conducted to determine a reasonable expectation
for secondary treatment capacity through the year. It was determined that
the secondary plant could reliably treat the following flows:
Summer140 ML/d
Spring-Fall160 ML/d
Winter260 ML/d
The seasonal differences reflect the affect upon the aeration system
of the differing oxygen transfer characteristics, bacterial respiration
rates, and environmental conditions through the course of a year.
Interim Process Features. Secondary treatment flows were controlled
by modulating the primary effluent bypass gates to maintain a constant
head in the primary effluent channels. The flow is directed through the
trickling filter pump station area to a series of bypass gates that connect
to the mixed liquor channel feeding the solids contact tanks. By only
partially opening one of these gates, it acts as an orifice and at a relatively
constant upstream head, admits a constant flow into the secondary treatment
area.
The possibility of sludge bulking was addressed by installing a temporary
hypochlorite system. Typical SVIs through the first several months of
operation have been in the range of 170 mL/g. As there is significant
excess secondary clarifier capacity at the present flows and the SVIs
have not proven excessive, the temporary hypochlorite system has not been
used.
Sludge is wasted at a constant rate from the reaeration tank to maintain
the target SRT range - 2.0 to 2.5 days. As the mixed liquor concentration
tends to vary, the rate of wasting is moderated while maintaining the
SRT within the desired range.
Process Performance Data. Startup and commissioning
of the Phase 1 Secondary plant commenced during mid March
1997. The system was seeded with 90 m3 of thickened waste
activated sludge obtained from another nearby plant. Within
a few weeks, the process had stabilized and was generally
achieving the effluent quality expected. Figure 3 illustrates
the BOD and Figure 4 shows the TSS for the period starting
April 1 and ending June 20 1997.
During this period, the flows averaged approximately 180 ML/d. The average
TSS was 8.2 mg/L and the average BOD, 10.1 mg/L. A slight
upset during the second week of April coincident with the
startup of secondary sludge thickening was quickly rectified
and the system has been stable since that time. Only once
during the upset period did the BOD exceed the limit of
30 mg/L while the TSS has not exceeded the 40 mg/L standard.
During this period, the TSS load to the Fraser River has
been decreased by about 5,000 kg/d and the BOD load has
been decreased by about 6,500 kg/d.
ODOUR
TREATMENT
The Annacis Island WWTP is located within a populated
light and heavy industrial zoned area. Additionally, the
plant is located immediately adjacent to a major arterial
overhead traffic bridge that passes thousands of cars daily.
Odour treatment systems were provided for both liquid stream
and solids handling facilities. The liquid stream processes
are served by two major odour treatment systems: the primary
treatment odour control system which serves influent sewer
ventilation, preaeration, and gravity thickening; and the
secondary treatment odour control system which serves trickling
filters, solids contact tanks, and mixed liquor conveyance
channels. Each system has its own foul air collection network
and treatment system. Both systems use the same process
design for odour treatment.

Process Concept Development. Figure 5 illustrates the odour treatment
process flowsheet used for both systems. The GVS&DD made an early
decision to embrace the use of biofilter technology for odour removal.
Biofilters demonstrated excellent removal performance for a wide range
of organic and inorganic odourous compounds, including sulphides. There
was information which showed that applying too much sulphide to a biofilter
could result in too much sulphuric acid production which would ultimately
destroy the filter beds ability to host odour removing microorganisms.
The raw sewage contained high sulphide levels and it was probable that
hydrogen sulphide concentrations in foul air could peak in the 20 - 50
ppm range. With these considerations, a process flowsheet was developed
with scrubbing towers for peak sulphide removal followed by biofilters
for removal of all other odorous compounds.
Table 4Packed Bed Scrubbers
Design Data
| Item |
Primary Treatment Odour
Control System |
Secondary Treatment
Odour Control System |
| Foul air flow, per
scrubber, L/s |
9,900 |
11,250 |
| Number |
2 |
2 |
| Vessel material |
FRP |
FRP |
| Diameter, m |
3.0 |
3.6 |
| Height, m |
8.23 |
8.70 |
| Packing height, m |
3.0 |
3.0 |
| Liquid recirculation
rate, L/s |
25 |
32 |
| Blow down rate, L/s |
0.25-2.5 |
0.32 - 3.2 |
| Operating pH |
11 - 11.5 |
11 - 11.5 |
| Odour removal efficiency,
percent |
99 |
99 |
|
For the scrubbing tower portion of the flowsheet, a traditional caustic/hypochlorite
scrubbing system was compared against a caustic only scrubbing system.
Caustic/hypochlorite scrubbing systems are more typical because the hypochlorite
oxidizes the absorbed sulphides as well as a range of other absorbed odourous
compounds. A concern with caustic only scrubbers is that absorbed odorous
compounds are not oxidized and can be re-released when spent scrubbing
solution is discharged back into the treatment plant liquid stream. For
this application, two factors mitigated the concerns related to a caustic
only system; the scrubbers main purpose was to protect the downstream
biofilter from excessive sulphides as the biofilter was expected to remove
most other odourous compounds, and spent scrubber solution could be discharged
to the highly oxidizing conditions of the solids contact tank to promote
oxidation of absorbed sulphides. The operational savings associated with
not utilizing hypochlorite in the scrubbing solution were estimated at
over $500,000 per year. For the cost savings and the mitigation of potential
concerns, the decision was made to not utilize hypochlorite in the scrubber
system.
Caustic Scrubber/Biofilter Design Features. Table 4 describes
the design data for the packed bed scrubber systems. Packed bed scrubbers
reduce the concentration of odourous compounds (primarily hydrogen sulphide)
with a dilute caustic soda solution. Caustic soda creates an alkaline
solution that has a high affinity for acid, such as hydrogen sulphide,
and therefore absorbs acid gases from the air. Caustic soda, at 25 percent
concentration, is supplied by truck and stored in a bulk storage tank.
A portion of the scrubbing solution is pumped to the solids contact tanks
for disposal. The aerobic biomass within the reaeration tanks oxidizes
the sulphide ions into soluble sulphate ions and elemental sulphur.
Foul air enters the bottom of a scrubber, flows upward through random
packing, through a demister, and exits the top of the scrubber. Two variable
speed blowers, located between the scrubbers and the biofilters, force
the partially treated foul air from the scrubbers to the biofilters. If
bypassing the biofilters is desired, the scrubbers can discharge directly
to the atmosphere. During periods of low sulphide production (winter)
the packed bed scrubbers can be bypassed to send foul air directly to
the biofilters.
Table 5 describes the design data for the biofilters. The biofilters
are either the second treatment stage or the only treatment stage of foul
air. Biofilters reduce the concentration of odorous compounds by absorbing
them onto the filter media, where microbial oxidation occurs.
Table 5 Biofilters Design
Data
| |
Primary Treatment Odour
Control System |
Secondary Treatment
Odour Control System |
| Capacity, L/s |
19,800 |
22,500 |
| Air velocity, m/min |
0.9 |
0.9 |
| Biofilter active base
area, m2 |
1,350 |
1,440 |
| Media depth, mm |
900 |
900 |
|
To compensate for varying pressures, variable frequency drives regulate
the speed of the biofilter blowers. As the pressure in a biofilter changes,
the flow controller maintains a set flow rate and provides a constant
flow of foul air to the media. For uniform distribution, the foul air
is diffused beneath the media by perforated piping.
The media layers include a base liner, a graded gravel underdrain, a
pea gravel layer for air dispersion, a bark layer, and the main media
consisting of a combination of bark mulch, peat moss, topsoil, and oyster
shells. An automatic sprinkler system provides water to keep the media
moist during dry weather periods.
OTHER
FEATURES
Influent Pumping. For the secondary treatment project
the firm influent pumping capacity was required to be upgraded. The original
pumping station incorporated bar screens with 25mm spacing. It was determined
that with the installation of trickling filters in the secondary process,
screens with 12mm spacing would be required. After an evaluation of alternatives,
it was concluded that construction of a new influent pumping station,
with new climber-type bar screens, would be more economical than expanding
the existing station and replacing the existing screens. The existing
station is being converted to a maintenance facility.
Three 6.3 m3/s influent pumps lift screened raw sewage from the wet well
to the influent channel of the preaeration tanks. Pump speed and the number
of pumps operating is varied based on the water level in the wet well.
This allows the wet well to be relatively small. There are three influent
pumps which are vertical mixed flow dry pit units, each driven by an 1100
hp, 275 rpm electric motor, with variable frequency drive.
The new influent pumping station includes screenings handling facilities
as well as mechanically-raked bar screens. Screenings are raked from the
screen bars into shaftless screw conveyors and directed to pneumatic ejector
vessels. At preset intervals, the screenings are pneumatically transferred
from the ejector vessels to screenings compactors in the screenings handling
area. The compactors dewater and compact the screenings that are then
discharged to screenings hoppers located above truck bays.
Primary Treatment Improvements. As the project was basically an
upgrading of a primary treatment plant to secondary treatment, modifications
to the primary treatment area were limited to those necessary to incorporate
secondary treatment. These included reconstruction of the influent channel
which feeds the preaeration (grit) tanks, covering of the preaeration
tanks to allow foul air collection and replacement of the sedimentation
tank v-notch weirs with submerged launders. The submerged launders reduce
odour production and allow sedimentation tank level to be controlled by
varying the trickling filter pump speed. Hydraulically operated sluice
gates were installed at the end of the primary effluent channel to divert
primary effluent to the new secondary treatment facilities while still
allowing emergency bypass of primary effluent to the outfall.
SUMMARY
Over the 1990s decade, the GVS&DD has engaged in the
process of bringing about a comprehensive upgrade to secondary treatment
at the Annacis Island WWTP which serves a population equivalent of nearly
one million. A comprehensive selection protocol resulted in choosing the
TF/SC process for providing secondary treatment. New large trickling filters,
aerated solids contact tanks, secondary clarifiers and an array of other
related facilities and improvements resulted in a project valued at nearly
$470 million CDN. An interim Phase 1 Secondary Treatment process was successfully
commissioned which used the aerated solids contact tanks and secondary
clarifiers to provide full activated sludge secondary treatment to a portion
of the plant flow for about a one year period prior to completion of the
trickling filters. The trickling filters are expected to be commissioned
in late 1998, thereby allowing secondary treatment of design flows. The
plant's proximity to nearby businesses and a major commuter bridge required
that odour treatment facilities be built for both primary treatment and
secondary treatment facilities. Odour treatment was achieved with use
of caustic only scrubbers for sulphide removal followed by biofilters
for foul air polishing. The entire Annacis Island Secondary Treatment
Upgrade project is anticipated to be complete in the year 2000.
REFERENCES
Parker D., Krugel S., McConnell H., Littleford D., Palsenbarg R.,
and Esping D. (1993). Selecting the TF/SC process for secondary treatment
for Vancouver, Canada. Proceedings of the 66th Annual Conference of
the Water Environment Federation.
|